Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 134,1kW prp ; 148,1kW standby
- Manufacturer: BAUDOUIN
- Model: 6M11G165.5
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 6-L
- Bore and Stroke: 105 x 130 mm
- Displacement: 6,75 L
- Cooling System: Liquid (water + 50% glycol)
- Lube Oil Specifications: API CF or CH4, SAE 15W-40
- Compression Ratio: 18:1
- Fuel Consumption ESP: 36,1 l/h
- Fuel Consumption 100% PRP: 32,7 l/h
- Fuel Consumption 75 % PRP: 24,5 l/h
- Fuel Consumption 50 % PRP: 16,7 l/h
- Fuel Consumption 25 % PRP: 9,3 l/h
- Lube oil consumption with full load: 0,2 % of fuel consumption
- Total oil capacity including tubes, filters 19 L
- Total coolant capacity: 17 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 80 mm
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 12V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Radiator water level sensor (Optional)
- Generator: STAMFORD
- Model: UCI274F
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-3 11"1/2
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 550 ºC
- Exhaust Gas Flow: 30,12 m3/min
- Maximum allowed back pressure: 60 mbar
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 546 m3/h
- Cooling Air Flow: 5,08 m3/s
- Alternator fan air flow: 0,514 m3/s
- - STARTING SYSTEM.
- Starting power: 4 kW
- Starting power: 5,44 CV
- Recommended battery: 44 Ah
- Auxiliary Voltage: 12 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Maximum power suction pump: 375 mm Hg
- Maximum return feed pump: 375 mm Hg
- Fuel Tank: 250 L
- - DIMENSIONS.
- Length: 2.900 mm
- Height: 1.480 mm
- Width: 900 mm
- Maximum shipping volume: 3,86 m3
- Weight with liquids in radiator and sump: 1.497 kg
- Fuel tank capacity: 250 L
- Autonomy: 10 Hours
Length (A)290114.17
Width (B)9035.43
Height (C)14858.27
Weight with fluids in radiator and crankcase
1497
3300.885