Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 144,3kW prp ; 161,3kW standby
- Manufacturer: PSI
- Model: 14.6L
- Engine Type: 4-stroke Otto Cycle
- Injection Type: Carburization
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 8-V
- Bore and Stroke: 128 x 142 mm
- Displacement: 14,6 L
- Cooling System: Coolant
- Lube Oil Specifications: API CD/≥CF, SAE 15W40
- Compression Ratio: 10,5:1
- Total oil capacity including tubes, filters 38,1 L
- Total coolant capacity: 127 L
- Governor Type Electrical
- Air Filter Type Dry
- LPG-liquefied petrol gas engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Dry air filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: UCI274G
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-1 14"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - SOUNDPROOFED VERSION.
- Steel chassis
- Anti-vibration shock absorbers
- External emergency stop switch
- Bodywork made from high quality steel plate
- High mechanical strength
- Low noise emissions level
- Soundproofing provided by high-density volcanic rock wool
- Epoxy polyester powder coating
- Full access for maintenance (water, oil and filters, no need to remove the canopy)
- Reinforced lifting hooks for crane hoisting
- Watertight chassis (acts as a double barrier against liquid retention)
- Chassis drain plug
- Steel residential silencer -35db(A) attenuation.
- Oil sump extraction kit
- IP Protection according to ISO 8528-13:2016
- - GAS RAMP.
- Manual shut-off valve
- Gas filter
- Double solenoid valve
- Primary pressure regulator
- Secondary pressure regulator (Zero pressure regulator)
- Low pressure switch
- Valve (tightness) testing system
- Inlet pressure manometer
- Outlet pressure manometer
- Special Start/Stop sequence
- High pressure regulator (Optional)
- High pressure switch (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 750 ºC
- Exhaust Gas Flow: 45,2 m3/min
- Maximum allowed back pressure: 10,2 kPa
- Exhaust Flange Size (external diameter): 200 mm
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 840 m3/h
- Alternator fan air flow: 0,514 m3/s
- - STARTING SYSTEM.
- Starting power: 7 kW
- Starting power: 9,52 CV
- Recommended battery: 200 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: LPG
- - DIMENSIONS.
- Length: 5.000 mm
- Height: 2.369 mm
- Width: 2.100 mm
- Maximum shipping volume: 24,87 m3
- Weight with liquids in radiator and sump: 5.016 kg
- Sound pressure level: 70 ± 2,4 dB(A)@7m
Length (A)500196.85
Width (B)21082.68
Height (C)236.993.27
Weight with fluids in radiator and crankcase
5016
11060.28