Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 138,5kW cop ; 174,9kW prp ; 193,1kW standby
- Manufacturer: FPT_IVECO
- Model: N67.TE3PV
- Engine Type: 4-stroke diesel
- Injection Type: Direct, common rail
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 6-L
- Bore and Stroke: 104 x 132 mm
- Displacement: 6,7 L
- Cooling System: Coolant
- Lube Oil Specifications: 10W40 CJ4 / CK4 ACEA E9
- Compression Ratio: 16,5:1
- Fuel Consumption ESP: 47,6 l/h
- Fuel Consumption 100% PRP: 43,9 l/h
- Fuel Consumption 80 % PRP: 41,2 l/h
- Fuel Consumption 50 % PRP: 29,4 l/h
- Fuel Consumption 25 % PRP: 14,1 l/h
- Lube oil consumption with full load: 0,3 % of fuel consumption
- Total oil capacity including tubes, filters 17 L
- Total coolant capacity: 36,2 L
- Governor Type Electrical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 12V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: UCI274H
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-3 11"1/2
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- High mechanical strength
- Epoxy polyester powder coating
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 600 ºC
- Maximum allowed back pressure: 20 kPa
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 682,35 m3/h
- Cooling Air Flow: 3,8 m3/s
- Alternator fan air flow: 0,514 m3/s
- - STARTING SYSTEM.
- Auxiliary Voltage: 12 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 250 L
- - DIMENSIONS.
- Length: 2.900 mm
- Height: 1.634 mm
- Width: 900 mm
- Maximum shipping volume: 4,26 m3
- Weight with liquids in radiator and sump: 1.570 kg
- Fuel tank capacity: 250 L
- Autonomy: 6 Hours
Length (A)290114.17
Width (B)9035.43
Height (C)163.464.33
Weight with fluids in radiator and crankcase
1570
3461.85