Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 269,6kW cop ; 342,6kW prp ; 377,6kW standby
- Manufacturer: FPT_IVECO
- Model: C13TE2F
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 6-L
- Bore and Stroke: 135 x 150 mm
- Displacement: 12,88 L
- Cooling System: Liquid (water + 50% glycol)
- Lube Oil Specifications: ACEA E3 - E5
- Compression Ratio: 16,5:1
- Fuel Consumption ESP: 97,4 l/h
- Fuel Consumption 100% PRP: 92,9 l/h
- Fuel Consumption 80 % PRP: 81 l/h
- Fuel Consumption 50 % PRP: 53 l/h
- Lube oil consumption with full load: 0,2 % of fuel consumption
- Total oil capacity including tubes, filters 35 L
- Total coolant capacity: 67 L
- Governor Type Electrical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: MECC ALTE
- Model: ECO40.1S4C
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-1 14"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- High mechanical strength
- Epoxy polyester powder coating
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 520 ºC
- Maximum allowed back pressure: 5 kPa
- Heat dissipated by exhaust pipe: 591 KCal/Kwh
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 1770 m3/h
- Cooling Air Flow: 9,1 m3/s
- Alternator fan air flow: 0,9 m3/s
- - STARTING SYSTEM.
- Starting power: 5,5 kW
- Starting power: 7,48 CV
- Recommended battery: 185 x 2 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 597 L
- - DIMENSIONS.
- Length: 3.310 mm
- Height: 1.783 mm
- Width: 1.390 mm
- Maximum shipping volume: 8,2 m3
- Weight with liquids in radiator and sump: 2.974 kg
- Fuel tank capacity: 597 L
- Autonomy: 7 Hours
Length (A)331130.32
Width (B)13954.72
Height (C)178.370.20
Weight with fluids in radiator and crankcase
2974
6557.67