Region EUROPE

    Power Solutions

    HP RANGE

    HP RANGE

    Frequency
    Power
    Power range
     
    Version
    Model: HGS-1010 T5 BIO Soundproof 40FT-HC
    Model: HGS-1010 T5 BIO Open Skid Estático Estándar

    Model

    HGS-1010 T5 BIO

    HGS-1010 T5 BIO | Three phase | Biogas | Open Skid

    Model

    Powered by SIEMENS

    Alternator STAMFORD

    PRP
    ESP
    COP
    Power kVA
    1009
    Power kW
    1009
    Generator set data sheet
    • Engine Specifications 1.500 r.p.m.
    • Rated Engine Output: 1040kW cop
    • Manufacturer: SIEMENS
    • Model: SGE42HM
    • Engine Type: 4-stroke Otto Cycle
    • Injection Type: Carburization
    • Aspiration Type: Turbocharged
    • Number of cylinders and arrangement: 12-V
    • Bore and Stroke: 160 x 175 mm
    • Displacement: 42,2 L
    • Cooling System: Water + Antifreeze
    • Lube Oil Specifications: SAE 40
    • Compression Ratio: 11,9
    • Fuel Consumption 100% PRP: 2425 kW
    • Fuel Consumption 80 % PRP: 1979 kW
    • Fuel Consumption 75 % PRP: 1887,8 kW
    • Fuel Consumption 50 % PRP: 1325 kW
    • Fuel Consumption 25 % PRP: 72473 kW
    • Lube oil consumption with full load: 0,15
    • Total oil capacity: 403 L
    • Governor Type Electrical
    • Air Filter Type Dry
    • Biogas Engine
    • 4-stroke cycle
    • Water-cooled
    • Radiator with pusher fan
    • HTW sender
    • LOP sender
    • Electronic governor
    • Hot parts protection
    • Moving parts protection
    • Generator: STAMFORD
    • Model: PI734C
    • Poles: 4
    • Connection type (standard): Star
    • Mounting type: S-00 18"
    • Insulation: H class
    • Enclosure (according IEC-34-5): IP23
    • Exciter system: Self-excited, brushless
    • Voltage regulator: A.V.R. (Electronic)
    • Bracket type: Double drive-shaft
    • Coupling system: Elastic Coupling
    • Coating type: Standard (Vacuum impregnation)
    • - OPEN SET VERSION.
    • Emergency stop button
    • Steel chassis
    • Steel industrial silencer -15db(A) attenuation
    • Steel residential silencer -35db(A) attenuation.
    • - GAS RAMP.
    • Manual shut-off valve
    • Double solenoid valve
    • High pressure regulator
    • Primary pressure regulator
    • Secondary pressure regulator (Zero pressure regulator)
    • High pressure switch
    • Valve (tightness) testing system
    • Inlet pressure manometer
    • Outlet pressure manometer
    • Special Start/Stop sequence
    • - ELECTRICAL SYSTEM.
    • Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
    • Battery charger (standard on gensets with automatic control panels)
    • Heating resistor (standard on sets with automatic control panels)
    • Battery charger alternator with ground connection
    • Starter battery/ies installed (cables and bracket included)
    • Ground connection electrical installation with connection ready for ground spike (not supplied)
    • - EXHAUST SYSTEM.
    • Maximum exhaust temperature: 433 ºC
    • Exhaust Gas Flow: 1,47 kg/s
    • Maximum allowed back pressure: 450 mm H2o
    • - NECESSARY AMOUNT OF AIR.
    • Cooling Air Flow: 20,22 m3/s
    • Alternator fan air flow: 2,69 m3/s
    • - STARTING SYSTEM.
    • Auxiliary Voltage: 12 Vdc
    • - FUEL SYSTEM
    • Fuel Oil Specifications: Biogas

    Dimensions

    Dimensions
    Length (A)00.00
    Width (B)00.00
    Height (C)00.00

    Weight

    Weight

    Weight with fluids in radiator and crankcase

    0

    0

    Fuel capacity

    0

    0

    Request a Quote

    Request a Quote

    By filling in this form you consent to have your information processed and recorded on our system and for the management of your relationship as a user, client, or candidate for employment Himoinsa.com.
    /privacy-policy/eng.html

     privacy policy *
    * Required fields
    COMPARE
    Compare
     

    Necessary

    Technical cookies are strictly necessary for our website to function and to be able to navigate through it. These types of cookies are those that, for example, allow us to identify you, give you access to certain restricted parts of the page if necessary, or remember different options or services already selected by you, such as your privacy preferences. Therefore, they are activated by default, your authorization is not required in this regard.

    Statistics

    The analysis cookies allow us to study the navigation of the users of our website in general (for example, which sections of the page are the most visited, which services are used the most and if they work correctly, etc.). Based on the statistical information on navigation on our website, we can improve both the operation of the page itself and the different services it offers. Therefore, these cookies do not have an advertising purpose, but only serve to make our website work better, adapting to our users in general. By activating them you will contribute to this continuous improvement.