Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 94kW prp ; 94kW standby
- Manufacturer: FPT_IVECO
- Model: F36.ETVP02.A94
- Engine Type: 4-stroke diesel
- Injection Type: Direct, common rail
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 4-L
- Bore and Stroke: 102 x 110 mm
- Displacement: 3,6 L
- Cooling System: Liquid (water + 50% glycol)
- Lube Oil Specifications: 10W-40 (API CJ-4, CK-4)
- Compression Ratio: 18,5:1
- Fuel Consumption ESP: 23,5 l/h
- Fuel Consumption 100% PRP: 23,5 l/h
- Fuel Consumption 80 % PRP: 18,4 l/h
- Fuel Consumption 50 % PRP: 11,5 l/h
- Fuel Consumption 25 % PRP: 6,5 l/h
- Lube oil consumption with full load: 0,25
- Total oil capacity including tubes, filters 9 L
- Governor Type Electrical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 12V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- LOP sender (Optional)
- Generator: STAMFORD
- Model: UCI274C
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-3 11"1/2
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - SOUNDPROOFED VERSION.
- Steel chassis
- Anti-leakage chassis, predisposed to retain liquids (retention tray)
- Manhole for fuel tank cleaning and drainage
- Tilting cap in the exhaust
- Manhole to fill the radiator
- Pre-installation or niche to house the quick connection hydraulic fittings for fuel transfer
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Bodywork made from high quality steel plate
- High mechanical strength
- Low noise emissions level
- Soundproofing provided by high-density volcanic rock wool
- Epoxy polyester powder coating
- Full access for maintenance (water, oil and filters, no need to remove the canopy)
- Oil sump extraction kit
- Emergency stop button (double emergency stop protection: Interior on the panel + Exterior on the bodywork)
- Mechanized for power cable output
- Door with window to visualize control panel, alarms and measurements
- Pressure locks
- IP Protection according to ISO 8528-13:2016
- - ELECTRICAL SYSTEM.
- M5 control panel with electronic CEM7 control unit and switched emergency stop
- Power panel with built-in circuit breaker plates
- Safety relay in output terminal board (thermal magnetic trip and alarm in control unit)
- Battery Switch
- M12 control panel with electronic DSE 7310 control unit and switched emergency stop
- Socket boxs IP67
- Adjustable earth leakage protection (time & sensitivity) standard in M12, with thermal magnetic protection
- Socket boxes with 2x16A (2Ph), 1x16A (3Ph), 1x32A (3Ph) y 1x63A (3Ph)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 740 ºC
- Maximum allowed back pressure: 220 mbar
- - NECESSARY AMOUNT OF AIR.
- Alternator fan air flow: 0,514 m3/s
- - STARTING SYSTEM.
- Auxiliary Voltage: 12 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 450 L
- - DIMENSIONS.
- Length: 2.910 mm
- Height: 1.900 mm
- Width: 1.140 mm
- Maximum shipping volume: 6,3 m3
- Fuel tank capacity: 450 L
- Autonomy: 24 Hours
- Sound pressure level: 65 ± 2,4 dB(A)@7m
Length (A)291114.57
Width (B)11444.88
Height (C)19074.80
Weight with fluids in radiator and crankcase
0
0