Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 71,9kW cop ; 89,9kW prp ; 98,9kW standby
- Manufacturer: FPT_IVECO
- Model: N45.TE2P
- Engine Type: 4-stroke diesel
- Injection Type: Direct, common rail
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 4-L
- Bore and Stroke: 104 x 132 mm
- Displacement: 4,5 L
- Cooling System: Coolant
- Lube Oil Specifications: SAE 15W40-CLASS T2; ACEA E7/04
- Compression Ratio: 17,5:1
- Fuel Consumption ESP: 24,2 l/h
- Fuel Consumption 100% PRP: 22,3 l/h
- Fuel Consumption 80 % PRP: 18,2 l/h
- Fuel Consumption 50 % PRP: 11,9 l/h
- Lube oil consumption with full load: 0,1 % of fuel consumption
- Total oil capacity including tubes, filters 12,8 L
- Total coolant capacity: 18,5 L
- Governor Type Electrical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 12V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: UCI274F
- Poles: 4
- Connection type (standard): Double delta
- Mounting type: S-3 11"1/2
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- High mechanical strength
- Epoxy polyester powder coating
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum allowed back pressure: 10 kPa
- Heat dissipated by exhaust pipe: 608 KCal/Kwh
- - NECESSARY AMOUNT OF AIR.
- Alternator fan air flow: 0,514 m3/s
- - STARTING SYSTEM.
- Recommended battery: 44 Ah
- Auxiliary Voltage: 12 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 170 L
- - DIMENSIONS.
- Length: 2.450 mm
- Height: 1.485 mm
- Width: 796 mm
- Maximum shipping volume: 2,9 m3
- Weight with liquids in radiator and sump: 1.263 kg
- Fuel tank capacity: 170 L
- Autonomy: 9 Hours
Length (A)24596.46
Width (B)79.631.34
Height (C)148.558.46
Weight with fluids in radiator and crankcase
1263
2784.915