Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 1684kW prp ; 1895kW standby
- Manufacturer: MITSUBISHI
- Model: S16R PTAA2
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 16-V
- Bore and Stroke: 170 x 180 mm
- Displacement: 65,37 L
- Cooling System: Water
- Lube Oil Specifications: API CD or CF SAE 30 or SAE 40
- Compression Ratio: 14,0:1
- Fuel Consumption ESP: 454,01 l/h
- Fuel Consumption 100% PRP: 402,12 l/h
- Fuel Consumption 75 % PRP: 307,58 l/h
- Fuel Consumption 50 % PRP: 215,04 l/h
- Fuel Consumption 25 % PRP: 124,5 l/h
- Lube oil consumption with full load: 0,8
- Total oil capacity including tubes, filters 230 L
- Total coolant capacity: 400 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 340 mm
- Oil temperature sensor
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: MECC ALTE
- Model: ECO46.1L4A
- Poles: 4
- Connection type (standard): Star - Parallel
- Mounting type: S-00 21"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery Switch
- Battery charger (standard on gensets with automatic control panels)
- Water Jacket Heater with single phase pump
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 560 ºC
- Exhaust Gas Flow: 420 m3/min
- Maximum allowed back pressure: 600 mm H2o
- Heat dissipated by exhaust pipe: 641,28 KCal/Kwh
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 9540 m3/h
- Cooling Air Flow: 41,66 m3/s
- Alternator fan air flow: 2,25 m3/s
- - STARTING SYSTEM.
- Starting power: 7,5 x 2 kW
- Starting power: 10,2 x 2 CV
- Recommended battery: 400 Ah
- Auxiliary Voltage: 24 Vdc
- Starter current peak: 1250 A
- Nominal starter current: 400 A
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Maximum power suction pump: 75 mm Hg
- Maximum return feed pump: 150 mm Hg
- Fuel Tank: 450 L
- - DIMENSIONS.
- Length: 6.120 mm
- Height: 2.700 mm
- Width: 2.190 mm
- Maximum shipping volume: 36,19 m3
- Weight with liquids in radiator and sump: 14.554 kg
- Fuel tank capacity: 450 L
- Autonomy: 1 Hours
Length (A)612240.95
Width (B)21986.22
Height (C)270106.30
Weight with fluids in radiator and crankcase
14554
32091.57