Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 651,9kW prp ; 701,9kW standby
- Manufacturer: BAUDOUIN
- Model: 6M33G825.5
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 6-L
- Bore and Stroke: 150 x 185 mm
- Displacement: 19,6 L
- Cooling System: Liquid (water + 50% glycol)
- Lube Oil Specifications: API CF or CH4, SAE 15W-40
- Compression Ratio: 15:1
- Fuel Consumption ESP: 182,7 l/h
- Fuel Consumption 100% PRP: 161,5 l/h
- Fuel Consumption 75 % PRP: 116,4 l/h
- Fuel Consumption 50 % PRP: 76,9 l/h
- Fuel Consumption 25 % PRP: 42,4 l/h
- Lube oil consumption with full load: 0,3 % of fuel consumption
- Total oil capacity including tubes, filters 64 L
- Total coolant capacity: 159 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 200 mm
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: MECC ALTE
- Model: ECO40 VL/4 B
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-1 14"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 550 ºC
- Exhaust Gas Flow: 171,3 m3/min
- Maximum allowed back pressure: 75 mbar
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 3090 m3/h
- Cooling Air Flow: 13,75 m3/s
- Alternator fan air flow: 0,9 m3/s
- - STARTING SYSTEM.
- Starting power: 8,5 kW
- Starting power: 11,56 CV
- Recommended battery: 75 x 2 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Maximum power suction pump: 375 mm Hg
- Maximum return feed pump: 375 mm Hg
- Fuel Tank: 400 L
- - DIMENSIONS.
- Length: 3.930 mm
- Height: 1.940 mm
- Width: 1.910 mm
- Maximum shipping volume: 14,56 m3
- Weight with liquids in radiator and sump: 5.781 kg
- Fuel tank capacity: 400 L
- Autonomy: 3 Hours
Length (A)393154.72
Width (B)19175.20
Height (C)19476.38
Weight with fluids in radiator and crankcase
5781
12747.105