Generator set data sheet
- Engine Specifications 1.800 r.p.m.
- Rated Engine Output: 873,8kW prp ; 965,8kW standby
- Manufacturer: BAUDOUIN
- Model: 12M26G900.6
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 12-V
- Bore and Stroke: 150 x 150 mm
- Displacement: 31,8 L
- Cooling System: Liquid (water + 50% glycol)
- Lube Oil Specifications: API CF4, SAE 15W40
- Compression Ratio: 15,7:1
- Fuel Consumption ESP: 242 l/h
- Fuel Consumption 100% PRP: 217,3 l/h
- Fuel Consumption 75 % PRP: 164 l/h
- Fuel Consumption 50 % PRP: 113,9 l/h
- Fuel Consumption 25 % PRP: 65,2 l/h
- Lube oil consumption with full load: 0,3 % of fuel consumption
- Total oil capacity including tubes, filters 114 L
- Total coolant capacity: 148 L
- Governor Type Electrical
- Air Filter Type Dry
- Inner diameter exhaust pipe: 200 mm
- Oil temperature sensor
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- LOP sender
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: HCI634H
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-0 18''
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- Fuel transfer pump (Optional)
- Steel industrial silencer -15db(A) attenuation (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery Switch
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 550 ºC
- Exhaust Gas Flow: 225,5 m3/min
- Maximum allowed back pressure: 75 mbar
- Exhaust Flange Size (external diameter): 200 mm
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 5166 m3/h
- Cooling Air Flow: 18 m3/s
- Alternator fan air flow: 1,961 m3/s
- - STARTING SYSTEM.
- Starting power: 10 kW
- Starting power: 13,6 CV
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Maximum power suction pump: 375 mm Hg
- Maximum return feed pump: 375 mm Hg
- Fuel Tank: 350 L
- - DIMENSIONS.
- Length: 4.150 mm
- Height: 2.130 mm
- Width: 1.900 mm
- Maximum shipping volume: 16,8 m3
- Weight with liquids in radiator and sump: 7.734 kg
- Fuel tank capacity: 350 L
- Autonomy: 2 Hours
Length (A)415163.39
Width (B)19074.80
Height (C)21383.86
Weight with fluids in radiator and crankcase
7734
17053.47