Generator set data sheet
- Engine Specifications 1.800 r.p.m.
- Rated Engine Output: 1057,4kW standby
- Manufacturer: MTU
- Model: 16V2000G76S
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 16-V
- Bore and Stroke: 135 x 156 mm
- Displacement: 35,7 L
- Cooling System: Water
- Lube Oil Specifications: SAE 40
- Compression Ratio: 16
- Fuel Consumption 100% Standby: 266,59 l/h
- Fuel Consumption 75 % Standby: 198,03 l/h
- Fuel Consumption 50 % Standby: 138,4 l/h
- Fuel Consumption 25 % Standby: 44,17 l/h
- Lube oil consumption with full load: 0,8 % of fuel consumption
- Total oil capacity: 102 L
- Total coolant capacity: 95 L
- Governor Type Electrical
- Air Filter Type Dry
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: HCI634J
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-0 18''
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Oil sump extraction kit
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Connection panel wired to the safety protection (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery Switch
- Battery charger (standard on gensets with automatic control panels)
- Water Jacket Heater with single phase pump
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 650 ºC
- Exhaust Gas Flow: 270 m3/min
- Maximum allowed back pressure: 85 mbar
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 6120 m3/h
- Alternator fan air flow: 1,961 m3/s
- - STARTING SYSTEM.
- Starting power: 7,5 kW
- Starting power: 10,2 CV
- Auxiliary Voltage: 24 Vdc
- Nominal starter current: 700 A
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 400 L
- - DIMENSIONS.
- Height: 2.430 mm
- Width: 1.963 mm
- Fuel tank capacity: 400 L
- Autonomy: 2 Hours
Length (A)476187.40
Width (B)196.377.28
Height (C)24395.67
Weight with fluids in radiator and crankcase
0
0