Generator set data sheet
- Engine Specifications 1.800 r.p.m.
- Rated Engine Output: 0kW cop ; 2195kW prp ; 0kW standby
- Manufacturer: YANMAR
- Model: 12GY175L.DF6S
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 12-V
- Bore and Stroke: 175 x 215 mm
- Displacement: 62,1 L
- Cooling System: Water
- Lube Oil Specifications: SAE 15W-40, API CI-4 o CK-4
- Fuel Consumption 100% PRP: 496,49 l/h
- Fuel Consumption 75 % PRP: 382,17 l/h
- Fuel Consumption 50 % PRP: 273,07 l/h
- Fuel Consumption 25 % PRP: 160,71 l/h
- Lube oil consumption with full load: 0,4
- Total oil capacity: 306 L
- Governor Type Electrical
- Air Filter Type Dry
- Oil temperature sensor
- Low coolant level sensor
- Exhaust gas compensator
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Standard air filter
- Standard fuel filter
- Standard oil filter
- Radiator with pusher fan
- Radiator water level sensor
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Water separator filter (visible level) (Optional)
- Generator: STAMFORD
- Model: S7L1D.J4
- Poles: 4
- Connection type (standard): Star
- Mounting type: S-00 21"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Double drive-shaft
- Coupling system: Elastic Coupling
- Coating type: Standard (Vacuum impregnation)
- - CONTAINER VERSION.
- Soundproofing provided by high-density volcanic rock wool
- High mechanical resistance
- Low level of noise emissions
- Door with window to visualize control panel, alarms and measurements
- Reinforced lifting points for crane hoisting and lower ones for transportation by forklift
- Residential steel silencer with -35dB attenuation and tilting cap in the exhaust
- Fuel tank integrated in the chassis
- Anti-vibration shock absorbers
- Steel chassis
- Manual oil extraction pump
- Robust construction designed for continuous or emergency applications
- Stainless steel fittings
- Emergency stops
- Easy access to the power connection
- Reinforced chassis for heavy range
- Easy access for chassis cleaning
- Silent-block with anti-corrosion protection between the genset and the chassis
- Easy access to fill radiator through the roof
- - ELECTRICAL SYSTEM CONTAINER.
- Control panel and emergency stop button
- Heating resistor
- Power panel
- Battery charger (standard on automatic control panels)
- Battery charge alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Power panel with safety protection in output terminals box (open thermal magnetic protection and alarm)
- Maintenance-free and anti-explosion battery
- Battery isolator
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 480 ºC
- Exhaust Gas Flow: 409 m3/min
- Maximum allowed back pressure: 6 kPa
- - NECESSARY AMOUNT OF AIR.
- Alternator fan air flow: 3,72 m3/s
- - STARTING SYSTEM.
- Starting power: 9 x 2 kW
- Starting power: 12,24 x 2 CV
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Fuel Tank: 2.000 L
- - DIMENSIONS.
- Length: 12.190 mm
- Height: 2.896 mm
- Width: 2.440 mm
- Maximum shipping volume: 86,14 m3
- Fuel tank capacity: 2.000 L
- Autonomy: 5 Hours
Length (A)1219479.92
Width (B)24496.06
Height (C)289.6114.02
Weight with fluids in radiator and crankcase
0
0