Generator set data sheet
- Engine Specifications 1.800 r.p.m.
- Rated Engine Output: 481kW prp ; 552kW standby
- Manufacturer: HYUNDAI
- Model: DP158LDS
- Engine Type: 4-stroke diesel
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 8-V
- Bore and Stroke: 128 x 142 mm
- Displacement: 14,618 L
- Cooling System: Coolant
- Lube Oil Specifications: API CH4 SAE 15W40 or 10W40
- Compression Ratio: 15:1
- Fuel Consumption ESP: 139,6 l/h
- Fuel Consumption 100% PRP: 127,1 l/h
- Fuel Consumption 75 % PRP: 92,9 l/h
- Fuel Consumption 50 % PRP: 62,3 l/h
- Fuel Consumption 25 % PRP: 35,2 l/h
- Lube oil consumption with full load: 0,5 % of fuel consumption
- Total oil capacity: 22 L
- Total coolant capacity: 79 L
- Governor Type Electrical
- Air Filter Type Dry
- Diesel engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Water separator filter (no visible level)
- Dry air filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Radiator water level sensor (Optional)
- Generator: MECC ALTE
- Model: ECO40 3S/4 B
- Poles: 4
- Connection type (standard): Star - Parallel
- Mounting type: S-1 14"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Anti-vibration shock absorbers
- Chassis with integrated fuel tank
- Fuel level gauge
- Fuel tank drain plug
- Steel industrial silencer -15db(A) attenuation
- Fuel transfer pump (Optional)
- Steel residential silencer -35db(A) attenuation. (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 567 ºC
- Exhaust Gas Flow: 108 m3/min
- Maximum allowed back pressure: 5,9 kPa
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 2196 m3/h
- Cooling Air Flow: 14,17 m3/s
- Alternator fan air flow: 1,08 m3/s
- - STARTING SYSTEM.
- Starting power: 7 kW
- Starting power: 9,52 CV
- Recommended battery: 200 x 2 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Diesel
- Maximum power suction pump: 225 mm Hg
- Maximum return feed pump: 450 mm Hg
- Fuel Tank: 740 L
- - DIMENSIONS.
- Length: 3.600 mm
- Height: 2.024 mm
- Width: 1.460 mm
- Maximum shipping volume: 10,64 m3
- Weight with liquids in radiator and sump: 3.221 kg
- Fuel tank capacity: 740 L
- Autonomy: 8 Hours
Length (A)360141.73
Width (B)14657.48
Height (C)202.479.69
Weight with fluids in radiator and crankcase
3221
7102.305