Generator set data sheet
- Engine Specifications 1.500 r.p.m.
- Rated Engine Output: 607kW prp ; 717kW standby
- Manufacturer: PSI
- Model: 40L
- Engine Type: 4-stroke Otto Cycle
- Injection Type: Direct
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 12-V
- Bore and Stroke: 150 x 185 mm
- Displacement: 39,2 L
- Cooling System: Coolant
- Lube Oil Specifications: SAE 15W40; API CD or CE
- Compression Ratio: 10,5:1
- Fuel Consumption ESP: 2088 kW
- Fuel Consumption 100% PRP: 1829 kW
- Fuel Consumption 75 % PRP: 1430 kW
- Fuel Consumption 50 % PRP: 1030 kW
- Fuel Consumption 25 % PRP: 632 kW
- Total oil capacity: 146 L
- Total coolant capacity: 172 L
- Governor Type Electrical
- Air Filter Type Dry
- Natural Gas engine
- 4-stroke cycle
- Water-cooled
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: S6L1D.C4
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-0 18''
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Emergency stop button
- Steel chassis
- Anti-vibration shock absorbers
- Steel industrial silencer -15db(A) attenuation
- Steel residential silencer -35db(A) attenuation.
- - GAS RAMP.
- Manual shut-off valve
- Gas filter
- Double solenoid valve
- High pressure regulator
- Primary pressure regulator
- Low pressure switch
- High pressure switch
- Valve (tightness) testing system
- Inlet pressure manometer
- Outlet pressure manometer
- Special Start/Stop sequence
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M12, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 639 ºC
- Exhaust Gas Flow: 104 m3/min
- Maximum allowed back pressure: 13 kPa
- - NECESSARY AMOUNT OF AIR.
- - STARTING SYSTEM.
- Starting power: 10 kW
- Starting power: 13,6 CV
- Recommended battery: 75 x 4 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Natural Gas
- - DIMENSIONS.
- Length: 4.500 mm
- Height: 2.400 mm
- Width: 2.200 mm
- Maximum shipping volume: 23,76 m3
Length (A)450177.17
Width (B)22086.61
Height (C)24094.49
Weight with fluids in radiator and crankcase
0
0