- Engine Specifications 1.800 r.p.m.
- Rated Engine Output: 142,5kW prp ; 168,5kW standby
- Manufacturer: PSI
- Model: 8.1LT
- Engine Type: 4-stroke Otto Cycle
- Injection Type: Carburization
- Aspiration Type: Turbocharged and after-cooled
- Number of cylinders and arrangement: 6-L
- Bore and Stroke: 111 x 139 mm
- Displacement: 8,1 L
- Cooling System: Coolant
- Lube Oil Specifications: API CD/≥CF, SAE 15W40
- Compression Ratio: 10,5 : 1
- Fuel Consumption ESP: 1.772.56 cfh
- Fuel Consumption 100% PRP: 1.535.99 cfh
- Fuel Consumption 75 % PRP: 1.214.66 cfh
- Fuel Consumption 50 % PRP: 875.69 cfh
- Fuel Consumption 25 % PRP: 529.65 cfh
- Total oil capacity including tubes, filters 27,5 L
- Total coolant capacity: 80 L
- Governor Type Electrical
- Air Filter Type Dry
- Natural Gas engine
- 4-stroke cycle
- Water-cooled
- 24V electrical system
- Dry air filter
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: UCI274E
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-2 11,5"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Single bearing
- Coupling system: Flexible disc
- Coating type: Standard (Vacuum impregnation)
- - OPEN SET VERSION.
- Steel chassis
- Emergency stop button
- Anti-vibration shock absorbers
- Steel industrial silencer -15db(A) attenuation
- Steel residential silencer -35db(A) attenuation. (Optional)
- - GAS RAMP.
- Manual shut-off valve
- Gas filter
- Double solenoid valve
- Primary pressure regulator
- Secondary pressure regulator (Zero pressure regulator)
- Low pressure switch
- Valve (tightness) testing system
- Inlet pressure manometer
- Outlet pressure manometer
- Special Start/Stop sequence
- High pressure regulator (Optional)
- High pressure switch (Optional)
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery Switch (Optional)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 750 ºC
- Exhaust Gas Flow: 31,9 m3/min
- Maximum allowed back pressure: 10,2 kPa
- - NECESSARY AMOUNT OF AIR.
- Intake air flow: 600 m3/h
- Alternator fan air flow: 0,617 m3/s
- - STARTING SYSTEM.
- Starting power: 4,5 kW
- Starting power: 6,12 CV
- Recommended battery: 150 Ah
- Auxiliary Voltage: 24 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Natural Gas
- - DIMENSIONS.
- Length: 3.000 mm
- Height: 1.621 mm
- Width: 1.160 mm
- Maximum shipping volume: 5,64 m3
- Weight with liquids in radiator and sump: 2.165 kg
Length (A)300118.11
Width (B)11645.67
Height (C)162.163.82
Weight with fluids in radiator and crankcase
2165
4773.825