Generator set data sheet
- Engine Specifications 1.800 r.p.m.
- Rated Engine Output: 1067kW cop
- Manufacturer: SIEMENS
- Model: SGE56SL
- Engine Type: 4-stroke Miller Cycle
- Injection Type: Carburization
- Aspiration Type: Natural
- Number of cylinders and arrangement: 16-V
- Bore and Stroke: 160 x 175 mm
- Displacement: 56,3 L
- Cooling System: Water + Antifreeze
- Lube Oil Specifications: SAE 40
- Compression Ratio: 12,3
- Fuel Consumption 100% PRP: 2813 kW
- Fuel Consumption 80 % PRP: 2309 kW
- Fuel Consumption 75 % PRP: 2205,07 kW
- Fuel Consumption 50 % PRP: 1580,42 kW
- Fuel Consumption 25 % PRP: 969,43 kW
- Lube oil consumption with full load: 0,2
- Total oil capacity: 272 L
- Governor Type Electrical
- Air Filter Type Semi-humid
- Natural Gas engine
- 4-stroke cycle
- Water-cooled
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: HCI634K
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-00 18"
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Double drive-shaft
- Coupling system: Elastic Coupling
- Coating type: Standard (Vacuum impregnation)
- - GAS RAMP.
- Manual shut-off valve
- Gas filter
- Double solenoid valve
- High pressure regulator
- Primary pressure regulator
- Low pressure switch
- High pressure switch
- Valve (tightness) testing system
- Inlet pressure manometer
- Outlet pressure manometer
- Special Start/Stop sequence
- - ELECTRICAL SYSTEM.
- Electric control and power panel with measurements devices and control unit (according to necessity and configuration)
- Battery Switch
- Adjustable earth leakage protection (time & sensitivity) standard in M5 and AS5, with thermal magnetic protection
- Battery charger (standard on gensets with automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charger alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 437 ºC
- Exhaust Gas Flow: 1,59 kg/s
- Maximum allowed back pressure: 450 mm H2o
- - NECESSARY AMOUNT OF AIR.
- Cooling Air Flow: 20,75 m3/s
- Alternator fan air flow: 1,961 m3/s
- - STARTING SYSTEM.
- Auxiliary Voltage: 12 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Natural Gas
Length (A)00.00
Width (B)00.00
Height (C)00.00
Weight with fluids in radiator and crankcase
0
0