Generator set data sheet
- Engine Specifications 1.800 r.p.m.
- Rated Engine Output: 350kW cop
- Manufacturer: SIEMENS
- Model: SGE18SL
- Engine Type: 4-stroke Otto Cycle
- Injection Type: Carburization
- Aspiration Type: Turbocharged
- Number of cylinders and arrangement: 6-L
- Bore and Stroke: 152 x 165 mm
- Displacement: 18 L
- Cooling System: Water + Antifreeze
- Lube Oil Specifications: SAE 40
- Compression Ratio: 11,6
- Fuel Consumption 100% PRP: 900 kW
- Fuel Consumption 80 % PRP: 753 kW
- Fuel Consumption 75 % PRP: 719,67 kW
- Fuel Consumption 50 % PRP: 532,55 kW
- Fuel Consumption 25 % PRP: 337 kW
- Lube oil consumption with full load: 0,35
- Total oil capacity: 86 L
- Governor Type Electrical
- Air Filter Type Semi-humid
- Natural Gas engine
- 4-stroke cycle
- Water-cooled
- Radiator with pusher fan
- HTW sender
- LOP sender
- Electronic governor
- Hot parts protection
- Moving parts protection
- Generator: STAMFORD
- Model: S4L1S.F
- Poles: 4
- Connection type (standard): Star-series
- Mounting type: S-0 18''
- Insulation: H class
- Enclosure (according IEC-34-5): IP23
- Exciter system: Self-excited, brushless
- Voltage regulator: A.V.R. (Electronic)
- Bracket type: Double drive-shaft
- Coupling system: Elastic Coupling
- Coating type: Standard (Vacuum impregnation)
- - CONTAINER VERSION.
- Soundproofing provided by high-density volcanic rock wool
- High mechanical resistance
- Low level of noise emissions
- Door with window to visualize control panel, alarms and measurements
- Reinforced lifting points for crane hoisting and lower ones for transportation by forklift
- Residential steel silencer with -35dB attenuation and tilting cap in the exhaust
- Anti-vibration shock absorbers
- Steel chassis
- Manual oil extraction pump
- Robust construction designed for continuous or emergency applications
- Stainless steel fittings
- Emergency stops
- Easy access to the power connection
- Reinforced chassis for heavy range
- Easy access for chassis cleaning
- Silent-block with anti-corrosion protection between the genset and the chassis
- Easy access to fill radiator through the roof
- - GAS RAMP.
- Manual shut-off valve
- Gas filter
- Double solenoid valve
- High pressure regulator
- Primary pressure regulator
- Low pressure switch
- High pressure switch
- Valve (tightness) testing system
- Inlet pressure manometer
- Outlet pressure manometer
- Special Start/Stop sequence
- - ELECTRICAL SYSTEM CONTAINER.
- Control panel and emergency stop button
- Power panel
- Battery charger (standard on automatic control panels)
- Heating resistor (standard on sets with automatic control panels)
- Battery charge alternator with ground connection
- Starter battery/ies installed (cables and bracket included)
- Ground connection electrical installation with connection ready for ground spike (not supplied)
- Battery isolator
- - EXHAUST SYSTEM.
- Maximum exhaust temperature: 397 ºC
- Exhaust Gas Flow: 0,46 kg/s
- Maximum allowed back pressure: 450 mm H2o
- - NECESSARY AMOUNT OF AIR.
- Cooling Air Flow: 6,83 m3/s
- Alternator fan air flow: 0,99 m3/s
- - STARTING SYSTEM.
- Auxiliary Voltage: 12 Vdc
- - FUEL SYSTEM
- Fuel Oil Specifications: Natural Gas
- - DIMENSIONS.
- Length: 6.058 mm
- Height: 2.896 mm
- Width: 2.438 mm
- Maximum shipping volume: 42,77 m3
Length (A)605.8238.50
Width (B)243.895.98
Height (C)289.6114.02
Weight with fluids in radiator and crankcase
0
0